ANSI/ISA | 5.01-2019 | Instrumentation Symbols and Identification | Mech EH | IS1 |
ANSI/ISA | 5.06.01-2007 | Functional Requirements Documentation for Control Software Applications | CDQ | IS2 |
ANSI/ISA | 12.01.01-2013 | Definitions and Information Pertaining to Electrical Equipment in Hazardous (Classified) Locations | EH | IS3 |
ANSI/ISA | 12.02.02-2014 | Recommendations for the Preparation, Content, and Organization of Intrinsic Safety Control Drawings | RMO | IS4 |
ANSI/ISA | 12.04.04-2012 | Pressurized Enclosures | Mech EH | IS5 |
ANSI/ISA | 12.12.01-2015 C22.2 NO. 213-15 | Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1 and 2 Hazardous (Classified) Locations | EH | IS6 |
ANSI/ISA | 18.2-2016 | Management of Alarm Systems for the Process Industries | CDQ | IS7 |
ANSI/ISA | 50.00.01-1975 (R2012) | Compatibility of Analog Signals for Electronic Industrial Process Instruments | CDQ EH EDH | IS8 |
ANSI/ISA | 71.04-2013 | Environmental Conditions for Process Measurement and Control Systems: Airborne Contaminants | EH | IS9 |
ANSI/ISA | 75.05.01-2019 | Control Valve Terminology | Mech | IS10 |
ANSI/ISA | 75.11.01-2013 | Inherent Flow Characteristic and Rangeability of Control Valves | Mech | IS11 |
ANSI/ISA | 75.13.01-2013 | Method of Evaluating the Performance of Positioners with Analog Input Signals and Pneumatic Output | EH EDH | IS12 |
ANSI/ISA | 75.25.01-2000 (R2010) | Test Procedure for Control Valve Response Measurement from Step Inputs | EH CDQ | IS13 |
ANSI/ISA | 75.26.01-2006 | Control Valve Diagnostic Data Acquisition and Reporting | EH CDQ | IS14 |
ANSI/ISA-TR | 77.70.01-2010 | Tracking and Reporting of Instrument and Control Data | CDQ | IS15 |
ANSI/ISA | 84.91.01-2012 | Identification and Mechanical Integrity of Safety Controls, Alarms, and Interlocks in the Process Industry | RMO | IS16 |
ANSI/ISA IEC | 95.00.01-2010 62264-1 Mod | Enterprise-Control System Integration – Part 1: Models and Terminology | SI RMO | IS17 |
ANSI/ISA | 95.00.02-2018 | Enterprise-Control System Integration – Part 2: Objects and Attributes for Enterprise-Control System Integration | SI RMO PM | IS18 |
ANSI/ISA IEC | 95.00.03-2013 62264-3 Modified | Enterprise-Control System Integration – Part 3: Activity Models of Manufacturing Operations Management | SI RMO PM | IS19 |
ANSI/ISA | 95.00.04-2018 | Enterprise-Control System Integration – Part 4: Objects and Attributes for Manufacturing Operations Management Integration | SI RMO PM | IS20 |
ANSI/ISA | 96.02.01-2007 | Guidelines for the Specification of Electric Valve Actuators | Mech EH | IS21 |
ANSI/ISA | 96.03.01-2012 | Guidelines for the Specification of Heavy Duty Pneumatically Powered Quarter Turn Valve Actuators | Mech | IS22 |
ANSI/ISA | 96.03.02-2015 | Guidelines for the Specification of Pneumatic Rack and Pinion Valve Actuators | Mech | IS23 |
ANSI/ISA | 96.03.03-2013 | Guidelines for the Specification of Pneumatic Vane Type Valve Actuators | Mech | IS24 |
ANSI/ISA | 101.01-2015 | Human Machine Interfaces for Process Automation Systems | CDQ | IS25 |
ANSI/ISA-TR ISA-TR | 12.12.04-2011 | Electrical Equipment in a Class I, Division 2/Zone 2 Hazardous Location | EH | IS26 |
ANSI/ISA-TR | 12.13.01-1999 (R2013) | Flammability Characteristics of Combustible Gases and Vapors | Mech | IS27 |
ANSI/ISA-TR | 75.25.02-2000 (R2010) | Control Valve Response Measurement from Step Inputs | CDQ | IS28 |
ANSI/ISA-TR | 104.00.03-2010 | EDDL: Meeting the requirements for integrating fieldbus devices in engineering tools for field devices | CDQ SI | IS29 |
ISA | 5.2-1976 (R1992) | Binary Logic Diagrams For Process Operations | CDQ EH EDH | IS30 |
ISA | 5.3-1983 | Graphic Symbols for Distributed Control/Shared Display Instrumentation, Logic, and Computer Systems | CDQ EH | IS31 |
ISA | 5.4-1991 | Instrument Loop Diagrams | NA | IS32 |
ISA | 5.5-1985 | Graphic Symbols for Process Displays | CDQ | IS33 |
ISA | 7.0.01-1996 | Quality Standard for Instrument Air | Mech EH RMO | IS34 |
ISA | 37.1-1975 (R1982) | Electrical Transducer Nomenclature and Terminology | EH | IS35 |
ISA | 37.16.01-2002 | A Guide for the Dynamic Calibration of Pressure Transducers | CDQ EH | IS36 |
ISA | 51.1-1979 (R1993) | Process Instrumentation Terminology | SI EH CDQ | IS37 |
ISA | 71.01-1985 | Environmental Conditions for Process Measurement and Control Systems: Temperature and Humidity | Mech EH | IS38 |
ISA | 71.02-1991 | Environmental Conditions for Process Measurement and Control Systems: Power | EH EDH | IS39 |
ISA | 71.03-1995 | Environmental Conditions for Process Measurement and Control Systems: Mechanical Influences | Mech RMO | IS40 |
ISA | 82.03-1988 | Safety Standard for Electrical and Electronic Test, Measuring, Controlling, and Related Equipment | RMO Mech EH EDH | IS41 |
Mechanical Derived Objectives and Requirements
Source ID Prefix | ANSI/ISA | International Society of Automation | OSHA |
Source ID Tag | 12.04.04-2012 | 75.11.01-2013 | 1910.242(b) |
Source Name | Pressurized Enclosures | Inherent Flow Characteristic and Rangeability of Control Valves | Hand and Portable Powered Tools and Other Hand-Held Equipment: Compressed air used for cleaning |
Project ID | IS5 | IS11 | OSHA 1910.242(b) |
Subsystem Objectives and Requirements Generated from Standards
Primary Level (Objective/Requirement) | Source | Project Reference [Project ID].[#] | Description |
Objective | IS5 | The system shall not fail due to over pressurization of gas enclosures. | |
Requirement | IS5 | IS5.1 | Pressure relief valves prevent the internal pressure of enclosures from exceeding (1 psi) above the protective gas supplies’ maximum operating pressure. |
Objective | IS5 | Protective gas enclosures/supplies shall not fail when subjected to the maximum operating pressure. | |
Requirement | IS5 | IS5.2 | The system can operate at 1.5 times the maximum operating pressure for at least 10 seconds. (Routine test) |
Objective | IS5 | Piping shall distribute compressed air to end user devices. | |
Requirement | IS5 | IS5.3 | Piping will abide by standard dimensions. |
Objective | IS5 | Electrical components mounted internally, and electrical components mounted through the enclosure shall be protected so that likely failure or abuse will not expose a hot surface or an ignition-capable arc to the external flammable atmosphere. | |
Objective | IS11 | The inherent flow characteristics of a control valve shall perform as specified by the manufacture’s standards. | |
Requirement | IS11 | IS11.1 | When performing a flow test of a control valve, the flow coefficient will not deviate by more than +-10 {1/Φ]^0.2 percent from the manufacturer-stated inherit flow characteristics. |